Outdoor Unit (Parts Ratings); Accessory Separate Sold Parts - Toshiba RAV-SM404SDT-E Service Manual

Split type
Hide thumbs Also See for RAV-SM404SDT-E:
Table of Contents

Advertisement

6-2. Outdoor Unit (Parts Ratings)

RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E
RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
No.
Parts name
1
Compressor
2
Outdoor fan motor
3
Reactor
4
4-way valve coil
5
PMV coil
6
P .C. board
7
Fuse (Mounted on P.C. board)
8
Fuse (Mounted on P.C. board)
9
Fuse (Mounted on P.C. board)
10
Outdoor temp. sensor (TO sensor)
11
Heat exchanger sensor (Te sensor)
12
Discharge temp. sensor (Td sensor)
13
Heat exchanger mid. Temp sensor (TL sensor)
14
Compressor thermo. (Protection)
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E
No.
Parts name
1
Fan motor
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To sensor)
5
Heat exchanger sensor (Te sensor)
6
Suction temp. sensor (Ts sensor)
7
Discharge temp. sensor (Td sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect))
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
12
Coil (Pulse Motor Valve)

6-3. Accessory Separate Sold Parts

RBC-U31PG (W, WS)-E (Ceiling panel), RBC-U31PGS (W, WS)-E (Ceiling panel)
RAV-SM564UT-E, RAV-SM804UT-E, RAV-SM1104UT-E, RAV-SM1404UT-E, RAV-SM1604UT-E
No.
Parts name
1
Motor-louver
2
Type
DA422A3F-25M
ICF-280-A100-1
CH-62
VHV-01AP552B1
UKV-A038
MCC-1571
US-622
Type
ICF-140-43-4R
DA150A1F-20F
CH-57
STF-01AJ502E1
US-622
CAM-MD12TF-6
Type
MP24ZN3N
– 45 –
Revised 2: Jun., 2008
Specifications
Output 100W
5.7mH, 18.5A
AC240V
DC12V
AC220 – 240V
AC250V, 25A
AC250V, 10A
AC250V, 3.15A
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
10 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C
Specifications
Output (Rated) 43W
3 phase, 4P, 1100W
10mH, 16A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
T3.15A, AC 250V
AC240V
OFF: 125 ± 4°C, ON: 90 ± 5°C
Specifications
DC 12 V