3-2. Outdoor Unit

RAV-SP1104AT-E, SP1104ATZ-E, SP1104ATZG-E, RAV-SP1404AT-E, SP1404ATZ-E, SP1404ATZG-E
Check joint
Cooling: High pressure
Heating: Low pressure
Accumulator
Rotary compressor
(2500cc)
(DA422A3F-25M)
RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E
Pressure
(MPa)
Pd
Ps
Standard
2.57
0.99
Cooling
Overload
3.30
1.09
Low load
1.74
0.75
Standard
2.32
0.73
Heating
Overload
3.22
1.17
Low load
2.17
0.30
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
*
meter becomes 2 times of No. of compressor revolutions (rps).
RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
Pressure
(MPa)
Pd
Ps
Standard
2.72
0.90
Cooling
Overload
3.34
1.07
Low load
1.75
0.76
Standard
2.59
0.69
Heating
Overload
3.13
1.05
Low load
2.40
0.21
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
*
meter becomes two times of No. of compressor revolutions (rps).
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
TS sensor
TL sensor
Heat exchanger
TD sensor
Ø8, 2 rows, 52 stages
FP1.45, flat fin
In cooling operation
In heating operation
Muffler
Muffler
Ø25 × L180
Ø25 × L210
Pipe surface temperature (°C)
(kg/cm²g)
Discharge
Suction
Pd
Ps
(TD)
(TS)
26.2
10.1
66
14
33.7
11.1
78
9
17.8
7.7
46
7
23.7
7.4
65
3
32.9
11.9
73
19
22.1
3.1
87
–15
Pipe surface temperature (°C)
(kg/cm²g)
Discharge
Suction
Pd
Ps
(TD)
(TS)
27.8
9.2
73
12
34.1
10.9
80
9
17.9
7.8
47
8
26.4
7.0
75
3
31.9
10.7
72
16
24.5
2.1
97
–22
www.heronhill.co.uk
TO sensor
TE sensor
Distributor
Strainer
Cooling: Low pressure
Heating: High pressure
Indoor heat
Outdoor heat
drive revolution
exchanger
exchanger
(TC)
(TL)
(TE)
12
44
38
13
49
43
5
32
25
39
2
3
54
14
15
38
–14
–13
Indoor heat
Outdoor heat
drive revolution
exchanger
exchanger
(TC)
(TL)
(TE)
10
46
38
13
51
45
6
33
25
43
2
2
53
12
13
42
–19
–18
– 37 –
PMV
Strainer
Capillary
Ø4 ×Ø3 (6 pcs.)
Refrigerant pipe
at liquid side Ø9.5
Packed valve
Refrigerant pipe
at gas side Ø15.9
Ball valve
Indoor/Outdoor
Compressor
temp. conditions
Indoor
(DB/WB) (°C)
frequency
fan
(rps)
Indoor
38
HIGH
27/19
53
HIGH
32/24
21
LOW
18/15.5
43
HIGH
20/–
26
LOW
30/–
71
HIGH
15/–
Indoor/Outdoor
Compressor
temp. conditions
Indoor
(DB/WB) (°C)
frequency
fan
(rps)
Indoor
51
HIGH
27/19
55
HIGH
32/24
21
LOW
18/15.5
53
HIGH
20/–
26
LOW
30/–
90
HIGH
15/–
Fax: 01823 665807
Outdoor
35/–
43/–
–5/–
7/6
24/18
–15/–
Outdoor
35/–
43/–
–5/–
7/6
24/18
–15/–