Enable Module; Connect The 3G8080(I)/Cd8080(I); Step 1: Connect Data Bus; Step 2: Connect Power - DSC PowerSeries Neo 3G8080 Installation Manual

Hspa/cdma controller
Hide thumbs Also See for PowerSeries Neo 3G8080:
Table of Contents

Advertisement

Mounted in Alarm Controller Cabinet
A Red wire on alarm controller PCLink_2 Header
B Antenna access ports
C Quad cables (100' / 30m maximum)
D Red wire on PCL-422 PCLink Header
E HSPA/CDMA Controller Board power terminals. Can be connected to power supply module (HSM2204/2300).

Enable Module

For the Alarm.com module to communicate with the panel, section [382] option 5 at the panel must be set to
ON. This section is OFF by default and must be enabled for the system to function properly. This should be
done before connecting the PC Link cable to power up the module to ensure all initialization commands are pro-
cessed properly.

Connect the 3G8080(I)/CD8080(I)

Caution: Ensure that the alarm panel is fully powered down (i.e., AC and battery disconnected) prior to con-
necting the 3G8080(I)/CD8080(I).

Step 1: Connect Data Bus

The maximum cable length permitted for the data bus is 100ft/30m.
Connect the RX+ terminal on the 3G8080(I)/CD8080(I) to the TX+ terminal on the PCL-422
l
Connect the RX- terminal on the 3G8080(I)/CD8080(I) to the TX- terminal on the PCL-422
l
Connect the TX- terminal on the 3G8080(I)/CD8080(I) to the RX- terminal on the PCL-422
l
Connect the TX+ terminal on the 3G8080(I)/CD8080(I) to the RX+ terminal on the PCL-422
l

Step 2: Connect Power

The maximum cable length permitted for the power connection is 100ft/30m.
Connect the GND terminal on the 3G8080(I)/CD8080(I) to the GND terminal on the PCL-422
l
Connect the +12V terminal on the 3G8080(I)/CD8080(I) to the +12V terminal on the PCL-422
l
E
D
+12V
GND
RX-
PCL-422
RX+
TX-
TX+
HSPA/CDMA Controller Board
+12V
GND
- 11 -