Operation Details

3. SOFT DRY OPERATION

A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal
setting temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
Soft Dry
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Condition
Model No.
Compressor OFF temperature = Compressor ON temperature.
The operation frequency changes every 30 seconds.
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues
for 3 minutes.
When the compressor stops operation, indoor fan stops for 330 seconds.
When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation
immediately.
When the Compressor stops, the outdoor fan motor stops 30 seconds later.
Cooling Operation
+1.5
+1.0
+0.5
15
0
15
–0.5
15
–3.5
Comp OFF
When the
temperature falls
CS-G93KE
– 20 –
Compressor Operation Frequency (Hz)
Cooling Operation
22
22
15
15
15
Comp OFF
Comp OFF
When the
When the
temperature rises
temperature falls
CS-G93KE
22
22
16
16
15
15
15
15
Comp OFF
When the
temperature rises
CS-G123KE