Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a.
Time Delay Safety Control
•
The compressor is not restarted for 3 minutes after stop of compressor.
b.
30 Second Forced Operation
•
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control
or Automatic switch.
c.
Total Running Current Control
•
When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not
exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running
current exceeds I2, the compressor is immediately stopped for 3 minutes.
<Cooling, Soft Dry set value>
Model No.
CU-G93KE
I1(A)
I2(A)
Note: Zone A will be used 30 minutes after operation starts.
<Heating set value>
Model No.
CU-G93KE
I1(A)
I2(A)
•
If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will
be turned off ; TIMER LED will blink and F98 is displayed.
d.
IPM (Power transistor) Prevention Control
1. Overheating Prevention Control
When the IPM (power transistor) temperature rises to 100 ± 10°C, the compressor stops immediately. The
•
compressor is restarted when the IPM (power transistor) temperature decreases to 90 ± 10°C after 3 minutes
(Time Delay Safety Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F96 is displayed
Zone A
CU-G123KE
CU-G93KE
5.3
6.7
7.3
10.8
Zone B
38.5°C
Zone A
CU-G123KE
6.1
9.2
7.3
10.8
Zone B
CU-G123KE
4.3
5.2
7.3
10.8
Outdoor air
temperature
37.5°C