Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a.
Time Delay Safety Control
The compressor is not restarted for 3 minutes after stop of compressor.
b.
30 Second Forced Operation
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control
or Automatic switch.
c.
Total Running Current Control
When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not
exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running
current exceeds I2, the compressor is immediately stopped for 3 minutes.
<Cooling, Soft Dry set value>
Model No.
CU-G93KE
I1(A)
I2(A)
Note: Zone A will be used 30 minutes after operation starts.
<Heating set value>
Model No.
CU-G93KE
I1(A)
I2(A)
If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will
be turned off ; TIMER LED will blink and F98 is displayed.
d.
IPM (Power transistor) Prevention Control
1. Overheating Prevention Control
When the IPM (power transistor) temperature rises to 100 ± 10°C, the compressor stops immediately. The
compressor is restarted when the IPM (power transistor) temperature decreases to 90 ± 10°C after 3 minutes
(Time Delay Safety Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F96 is displayed
Zone A
CU-G123KE
CU-G93KE
5.3
6.7
7.3
10.8
Zone B
38.5°C
Zone A
CU-G123KE
6.1
9.2
7.3
10.8
Zone B
CU-G123KE
4.3
5.2
7.3
10.8
Outdoor air
temperature
37.5°C
– 42 –