CS-G93KE
Operation Details
2. DC Peak Current Control
When the electric current to the IPM (power transistor) exceeds the set value, DC 27 ± 4A, the compressor
stops. The compressor restarts after 3 minutes.
If within 30 seconds the set value is exceeded again, the compressor will stop for 1 minute. If this condition
repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and F99 is displayed.
DC electric current
e.
Compressor Overheating Prevention Control
When the temperature of compressor rises to 105°C, the frequency is reduced as shown in diagram below.
When the temperature rises to 115°C or above, the compressor stops. The compressor will start operating
at low frequency when the temperature falls to 115°C and resume to normal condition when the temperature
falls to 94°C.
Compressor
temp. (°C)
Condition
The compressor stops when the temperature rises to 115°C. If this condition occurs 4 times within 20
minutes, all indoor and outdoors relays will be turned off; TIMER LED will blink and F97 is displayed.
f.
Low Pressure Control (Gas Leakage Detection)
When the following conditions as shown in the below table occur, the compressor stops and restarts after
3 minutes. If this phenomenon is continuously occuring twice within 30 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F91 is displayed.
Comp. Frequency *
Total Running
Current
Indoor Heat
Exchanger Temp.
Operation
Model No.
Note: The above conditions are not valid during Deice operation.
*
(A)
27±4
Comp. Off
3 min
3 min
30 sec
30 sec
Comp OFF
115
max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)
110
max 40Hz (CU-G93KE)
106
max 49Hz (CU-G123KE)
105
94
Free
When temperature rises
51 Hz and above
≥ 1.88 A and
*
< 1.9 A
15°C
or above
Cooling/Soft Dry
CU-G93KE
This conditions are continuous for 5 minutes.
Comp.
Off
1 min
30 sec
30 sec
1 min 30 sec
30 sec
7 times
Comp OFF
max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)
max 40Hz (CU-G93KE)
max 49Hz (CU-G123KE)
Free
When temperature falls
71 Hz and above
70 Hz and above
≥ 1.88 A and
≥ 1.88 A and
< 2.1 A
< 2.4 A
30°C
15°C
or below
or above
Heating
Cooling/Soft Dry
– 43 –
TIMER LED blinks
Comp.
F99 is displayed
Off
1 min
30 sec
1 min 30 sec
90 Hz and above
≥ 1.88 A and
< 2.7 A
30°C
or below
Heating
CU-G123KE