Operation Details
(b) Heating Operation
When the sleep button is pressed, the remote control setting temperature will decrease 2°C after 1 hour or
when the remote control setting temperature is reached. After another hour, 3°C will be decreased again.
When Sleep
button is pressed
* •
During sleep shift operation, indoor fan speed operates at Lo
13. DELAY ON TIMER CONTROL
When the Delay On Timer is set by using remote control, the unit will start to operate slightly earlier before the
set time, so that the room will nearly reach the set temperature by the On Timer set time.
60 minutes before the set time, the indoor fan operates at Lo
the indoor intake air temperature and outdoor air temperature in order to determine the starting time for
preparatory operation. (The Power LED blinks during sampling.)
The time of the preparatory operation will start before the On Timer set time.
a. Cooling/Soft Dry
Indoor
intake
air temp
(°C)
30
10 min
25
5 min
Outdoor air temp.
14. AUTO RESTART CONTROL
If there is a power failure, operation will automatically be restarted when the power is resumed from 2 minutes
58 seconds to 3 minutes 52 seconds randomly. It will start with the previous operation mode and airflow direction.
Auto Restart Control is not available when Timer or Sleep Mode is set.
J1 at indoor electronic controller should be open circuit when cancellation of Auto Restart Control.
Remote control
setting temperature
–2°C
1 hour
max 1 hour
Sleep mode shift
operation starts
15 min
30
35 (°C)
–3°C
8 hours
.
and outdoor fan operates for 20 seconds to sense
b. Heating
Indoor
intake
air temp
(°C)
15
35 min
5
45 min
0
Outdoor air temp.
– 40 –
CS-G93KE
All stop
25 min
5
(°C)