CS-G93KE
Operation Details
B. Deodorizing Control
•
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status
Compressor
Time (second)
Indoor Fan Speed
Compressor
Indoor
Fan Speed
When the compressor is in operation, the deodorizing status starts from 1 → 2 → 3.
•
When the compressor stops operation, the deodorizing status starts from 4 → 5 → 6 → 7.
•
•
If the compressor still stops operation after 3 minutes, the deodorizing status will start from 6.
C. Sensible Heat Control
•
This control is to improve the feeling in high fan speed during low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition.
1
2
3
ON
40
50
OFF
SLo
Auto
ON
OFF
– 19 –
4
5
6
OFF
30
60
30
SLo
OFF
SLo
OFF
7
6, 7, 6, 7,...
1
ON
60
.........
40
OFF
.........
OFF
ON