Operation Details
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
(ii) When the remote control setting temperature is 24°C and above.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
•
Compressor OFF temperature = Compressor ON temperature.
•
The operation frequency can be changed every 30 seconds.
•
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
•
The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and
continues for 3 minutes.
•
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
•
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
•
When the compressor stops, the outdoor fan motor stops 30 seconds later.
64 (Fc max) or 50
+1.5
36
+1.0
31
+0.5
15
0
15
–0.5
15
–1.0
Comp OFF
Less than 38°C
CS-G93KE
64 (Fc max) or 50
+1.5
36
+1.0
31
+0.5
15
0
15
–0.5
15
–1.0
Comp OFF
Less than 38°C
CS-G93KE
– 18 –
Compressor Operation Frequency (Hz)
64 (Fc max) or 50
92 (Fc max) or 70
40
31
22
15
15
Comp OFF
Comp OFF
38°C and above
Less than 38°C
Compressor Operation Frequency (Hz)
64 (Fc max) or 50
92 (Fc max) or 70
36
31
15
15
15
Comp OFF
Comp OFF
38°C and above
Less than 38°C
CS-G93KE
92 (Fc max) or 70
44
49
31
31
16
22
15
16
15
15
Comp OFF
38°C and above
CS-G123KE
92 (Fc max) or 70
44
44
31
31
16
16
15
15
15
15
Comp OFF
38°C and above
CS-G123KE