CS-G93KE
Operation Details
B. Deodorizing Control
•
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status
Compressor
Time (second)
Fan Speed
Compressor
Fan Speed
When the compressor is in operation, the deodorizing status starts from 1 → 2.
•
When the compressor stops operation, the deodorizing status starts from 3 → 4 → 5.
•
•
When the compressor stops operation, indoor fan stops for 330 seconds.
C. Sensible Heat Control
•
This control is to improve the feeling in high fan speed and low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition. (During Cooling operation).
1
2
ON
40
OFF
SLo
ON
ON
OFF
– 21 –
3
4
5
OFF
330
30
60
OFF
SLo
OFF
OFF
ON
OFF
4, 5, 4, 5,...
1
ON
.........
40
.........
OFF
ON