Operation Details
B. Deodorizing Control
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status
Compressor
Time (second)
Fan Speed
Compressor
Fan Speed
When the compressor is in operation, the deodorizing status starts from 1 → 2.
When the compressor stops operation, the deodorizing status starts from 3 → 4 → 5.
When the compressor stops operation, indoor fan stops for 330 seconds.
C. Sensible Heat Control
This control is to improve the feeling in high fan speed and low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition. (During Cooling operation).