Overview: Installation; Opening The Units; About Opening The Units; To Open The Outdoor Unit - Daikin Altherma ERLQ011-014-016CA Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERLQ011-014-016CA:
Table of Contents

Advertisement

Item
Description
15
Heat pump convector
Field supplied components
16
Shut-off valve
17
Electricity meter
18
Domestic hot water
pump
19
Alarm output
20
Changeover to external
heat source control
21
Space cool/heat
operation control
22
Power consumption
digital inputs
(a)
Refer to name plate on outdoor unit.
(b)
Minimum cable section 0.75 mm².
(c)
Cable section 2.5 mm².
(d)
The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.
(e)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
(f)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
use interface connection.
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
Backup heater
Power supply
type
*3V
1× 230 V
*9W
1× 230 V
3× 230 V
3× 400 V
7
Installation
7.1

Overview: Installation

This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
1
Mounting the outdoor unit.
2
Mounting the indoor unit.
3
Connecting the refrigerant piping.
4
Checking the refrigerant piping.
5
Charging refrigerant.
6
Connecting the water piping.
7
Connecting the electrical wiring.
8
Finishing the outdoor installation.
9
Finishing the indoor installation.
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
Wires
Maximum
running
current
(b)
4
100 mA
(b)
2
100 mA
(b)
2 (per meter)
(b)
2
(b)
2
(b)
2
(b)
2
(b)
2 (per input
signal)
Required number of
conductors
2+GND
2+GND + 2 bridges
3+GND + 1 bridge
4+GND
7.2

Opening the units

7.2.1

About opening the units

At certain times, you have to open the unit. Example:
▪ When connecting the refrigerant piping
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover
is removed.
7.2.2

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
2
1
7.2.3

To open the indoor unit

1 Loosen and remove the 2 screws that fix the front panel.
2 Tilt the front panel towards you and remove the front panel.
7 Installation
Installer reference guide
29