8 Configuration
#
Code
[A.6.3.1]
[4-08]
Mode:
▪ 0 (No limitation)(default): Disabled.
▪ 1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all the
time.
▪ 2 (Digital inputs): Enabled: You can
set up to four different power
limitation values (in A or kW) to
which
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2]
[4-09]
Type:
▪ 0 (Current): The limitation values are
set in A.
▪ 1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3]
[5-05]
Value: Only applicable in case of full
time power limitation mode.
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.4]
[5-09]
Value: Only applicable in case of full
time power limitation mode.
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1]
[5-05]
Limit DI1
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.2]
[5-06]
Limit DI2
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.3]
[5-07]
Limit DI3
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.4]
[5-08]
Limit DI4
0 A~50 A, step: 1 A (default: 50 A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
Limit DI1
0 kW~20 kW , step: 0.5 kW (default:
20 kW)
[A.6.3.6.2]
[5-0A]
Limit DI2
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.3]
[5-0B]
Limit DI3
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.4]
[5-0C]
Limit DI4
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
Priority: Only applicable in case of an optional EKHW.
Installer reference guide
70
Description
the
system
power
#
Code
[A.6.3.7]
[4-01]
Power consumption control
DISABLED [4‑08]=0
▪ 0 (None)(default): Backup heater and
booster
simultaneously.
▪ 1 (BSH): The booster heater is
prioritized.
▪ 2 (BUH): The backup heater is
prioritized.
Power consumption control
ENABLED [4‑08]=1 or 2
▪ 0 (None)(default): Depending on the
power limitation level, the booster
heater will be limited first, before the
backup heater is limited.
▪ 1 (BSH): Depending on the power
limitation level, the backup heater will
be limited first, before the booster
heater is limited.
▪ 2 (BUH): Depending on the power
limitation level, the booster heater
will be limited first, before the backup
heater is limited.
Note: In case of power consumption control is DISABLED (for all
models) the setting [4‑01] defines whether backup heater and
booster heater can operate simultaneously, or if the booster heater/
backup heater has priority over the backup heater/booster heater.
In case of power consumption control is ENABLED (only for EHBH/
X04+08 and EHVH/X04+08), the setting [4‑01] defines the priority of
the electrical heaters depending on applicable limitation.
#
Code
[A.6.3.7]
[4-01]
▪ 0 (None)(default): No heater is
prioritized. If the power consumption
control is enabled, the booster heater
will be limited first.
▪ 1 (BSH): The booster heater is
prioritized. If the power consumption
control is enabled, the backup heater
(step 1 and/or step 2) will be limited
first, before the booster heater is
limited.
▪ 2 (BUH): The backup heater is
prioritized. If the power consumption
control is enabled, the booster heater
will be limited first, before the backup
heater is limited.
Average timer
The average timer corrects the influence of ambient temperature
variations. The weather-dependent set point calculation is done on
the average outdoor temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1-0A]
Outdoor average timer:
▪ 0: No averaging (default)
▪ 1: 12 hours
▪ 2: 24 hours
▪ 3: 48 hours
▪ 4: 72 hours
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Description
heater
can
operate
Description
Description
Daikin Altherma – Low temperature split