8 Configuration
#
Code
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8-04].
Range: 0~10 hours (default: 3) (step: 1/2
hour) (only for EHBH/X).
Range: 0~10 hours (default: 0.5) (step:
1/2 hour) (only for EHVH/X).
Remark: The minimum time is 1/2 hour
even when the selected value is 0.
N/A
[8-03]
Booster heater delay timer.
Only for EKHW
Start-up delay time for the booster heater
when domestic hot water mode is active.
▪ When domestic hot water mode is
NOT
20 minutes.
▪ The delay time starts from booster
heater ON temperature.
▪ By adapting the booster heater delay
time versus the maximum running
time, you can find an optimal balance
between the energy efficiency and the
heat up time.
▪ If the booster heater delay time is set
too high, it might take a long time
before the domestic hot water reaches
its set temperature.
▪ The setting [8-03] is only meaningful if
setting [4-03]=1. Setting [4-03]=0/2/3
limits the booster heater automatically
in relation to heat pump operation time
in domestic water heating mode.
▪ Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
Range: 20~95 minutes (default: 50).
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
1
0
1
0
[8-00]
[8-01]
[8-02]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-03]: Booster heater delay timer
Installer reference guide
64
Description
active,
the
delay
time
is
t
1
4
0
1
3
0
1
0
1
0
[8-03]
1
Booster heater operation (1=active, 0=not active)
2
Heat pump domestic water heating mode (1=active, 0=not
active)
3
Hot water request for booster heater (1=request, 0=no
request)
4
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-04]: Additional running time at [4-02]/[F-01]
t
[8-01]+
[8-04]
[8-02]
[8-01]
0
[5-03]
[4-02]
T
T
Ambient (outdoor) temperature
A
t
Time
Anti-recycle time
Maximum running current
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.
#
Code
[A.4.4.2]
[2‑00]
Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1]
[2‑01]
Disinfection
▪ 0: No
▪ 1: Yes
[A.4.4.3]
[2‑02]
Start time: 00~23:00, step: 1:00.
ERHQ+ERLQ011~016 + EHBH/X11+16CB
t
t
[8-01]+
[8-04]
[8-02]
[8-01]
0
[F-01]
35C
A
Description
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
T
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma erhq011-014-016baAltherma ehbh/x11+16cb

Table of Contents