Multiple Rooms - One Lwt Zone - Daikin Altherma ERLQ011-014-016CA Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERLQ011-014-016CA:
Table of Contents

Advertisement

▪ A shut-off valve (field supply) is installed before the under  floor
heating to prevent condensation on the floor during cooling
operation.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4)
▪ The space operation mode is sent by one digital output (X2M/32
and X2M/33) on the indoor unit to:
▪ The heat pump convectors
▪ The shut-off valve
Configuration
Setting
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
External room thermostat for the
main zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
Benefits
▪ Cooling. Heat  pump convectors provide, besides heating
capacity, also excellent cooling capacity.
▪ Efficiency. Under  floor heating has the best performance with
Altherma LT.
▪ Comfort. The combination of the two heat emitter types provides:
▪ The excellent heating comfort of the under floor heating
▪ The excellent cooling comfort of the heat pump convectors
5.2.2
Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example: If the heat  pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Under floor heating or radiators – Thermostatic
valves
If you are heating up rooms with under floor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface or an
external room thermostat), while the other rooms are controlled by
so-called thermostatic valves, which open or close depending on the
room temperature.
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
Value
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
0 (1 LWT zone): Main
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
5 Application guidelines
Setup
A
B
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
User interface
▪ The under floor heating of the main room is directly connected to
the indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as thermostat.
▪ A thermostatic valve is installed before the under  floor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by
another heating source. Example: Fireplaces.
Configuration
Setting
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
Benefits
▪ Cost effective.
▪ Easy. Same installation as for one room, but with thermostatic
valves.
Under floor heating or radiators – Multiple external
room thermostats
Setup
A
B
M1
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
External room thermostat
b
Bypass valve
▪ For each room, a shut-off valve (field supplied) is installed to avoid
leaving water supply when there is no heating or cooling demand.
C
T
a
Value
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
0 (1 LWT zone): Main
C
b
M2
a
a
Installer reference guide
13