Daikin Altherma ERLQ011-014-016CA Installer's Reference Manual page 71

Low temperature split
Hide thumbs Also See for Altherma ERLQ011-014-016CA:
Table of Contents

Advertisement

INFORMATION
If the power saving function is activated (see [E‑08]), the
average outdoor temperature calculation is only possible in
case the external outdoor temperature sensor is used. See
"5.7  Setting up an external temperature sensor"  on
page 22.
Offset temperature external outdoor ambient sensor
Only applicable in case of an external outdoor ambient sensor is
installed and configured.
You can calibrate the external outdoor ambient temperature sensor.
It is possible to give an offset to the thermistor value. The setting can
be used to compensate for situations where the external outdoor
ambient sensor cannot be installed on the ideal installation location
(see installation).
#
Code
[A.6.5]
[2‑0B]
–5°C~5°C, step: 0.5°C (default: 0°C)
Forced defrost
You can manually start a defrost operation.
The decision to execute the manual defrost operation is made by the
outdoor unit and depends on ambient and heat exchanger
conditions. When the outdoor unit accepted the forced defrost
operation,
will be displayed on the user interface. If
displayed within 6  minutes after forced defrost operation was
enabled, the outdoor unit ignored the forced defrost request.
#
Code
[A.6.6]
N/A
Do you want to start a defrost operation?
Pump operation
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4‑02] or if
the outdoor temperature drops below the value set by [F‑01]. When
the pump operation is enabled, the pump operation is possible at all
outdoor temperatures.
#
Code
N/A
[F‑00]
Pump operation:
▪ 0: Disabled if outdoor temperature is
higher than [4‑02] or lower than [F‑01]
depending
operation mode.
▪ 1:
temperatures.
Pump operation during flow abnormality [F‑09] defines whether the
pump stops at flow abnormality or allow to continue operation when
flow abnormality occurs. This functionality is only valid in specific
conditions where it is preferable to keep the pump active when
T
<4°C (pump will be activated for 10 minutes and deactivated after
a
10 minutes). Daikin shall NOT be held liable for any damage
resulting this functionality.
#
Code
N/A
[F‑09]
Pump continue operation when flow
abnormality:
▪ 0: Pump will be deactivated.
▪ 1: Pump will be activated when
T
a
OFF)
Pump speed limitation
Pump speed limitation [9‑0D] defines the maximum pump speed. In
normal conditions, the default setting should NOT be modified. The
pump speed limitation will be overruled when the flow rate is in the
range of the minimum flow (error 7H).
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
Description
is NOT
Description
Description
on
heating/cooling
Possible
at
all
outdoor
Description
<4°C (10 minutes ON – 10 minutes
#
Code
N/A
[9‑0D]
Pump speed limitation
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation
required delta  T control and comfort
are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating/
cooling
limitation is applicable. When there is
heating/cooling
speed is only determined by delta T in
relation to the required capacity. With
this
possible
guaranteed.
8 Configuration
Description
in
all
conditions.
The
output,
the
pump
speed
output,
the
pump
limitation
range,
delta
T
is
and
the
comfort
is
Installer reference guide
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma erhq011-014-016baAltherma ehbh/x11+16cb

Table of Contents