Drain Pan Necessity - Daikin Altherma ERLQ011-014-016CA Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERLQ011-014-016CA:
Table of Contents

Advertisement

14 Technical data
14.8.3

Drain pan necessity

Entering water temperature limit to prevent condensation
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
1. Refer to psychometric chart for more information.
2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered.
Installer reference guide
132
Example:
With ambient temperature of 25°C
and relative humidity of 40%.
If entering water temperature is
below 12°C, condensation on water
piping will happen.
Dry bulb temperature [°C]
4D078990
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01