14 Technical data
14.5
Drain pan necessity
Entering water temperature limit to prevent condensation
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
1. Refer to psychometric chart for more information.
2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered.
Installer reference guide
92
Example:
With ambient temperature of 25°C
and relative humidity of 40%.
If entering water temperature is
below 12°C, condensation on water
piping will happen.
Dry bulb temperature [°C]
4D078990
ERLQ004~008CA + EHBH/X04+08CB
Daikin Altherma – Low temperature split
4P384972-1B – 2017.04