▪ The desired room temperature is set via the remote controller of
the heat pump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/35 and X2M/30).
▪ The space operation mode is sent to the heat pump convectors by
one digital output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat  pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heat pump convectors.
Configuration
Setting
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the
main zone:
▪ #: [2.A]
▪ Code: [C-05]
Benefits
▪ Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
▪ Efficiency. Optimal energy efficiency because of the interlink
function.
▪ Stylish.
Combination: Under floor heating + Heat pump
convectors
▪ Space heating is provided by:
▪ The under floor heating
▪ The heat pump convectors
▪ Space cooling is provided by the heat pump convectors only. The
under floor heating is shut off by the shut-off valve.
Setup
A
Main leaving water temperature zone
B
One single room
a
Remote controller of the heat pump convectors
▪ The heat  pump convectors are directly connected to the indoor
unit.
▪ A shut-off valve (field supply) is installed before the under  floor
heating to prevent condensation on the floor during cooling
operation.
Installer reference guide
12
Value
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
A
B
M1
a
▪ The desired room temperature is set via the remote controller of
the heat pump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/35 and X2M/30).
▪ The space operation mode is sent by one digital output (X2M/4
and X2M/3) on the indoor unit to:
▪ The heat pump convectors
▪ The shut-off valve
Configuration
Setting
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the
main zone:
▪ #: [2.A]
▪ Code: [C-05]
Benefits
▪ Cooling. Heat  pump convectors provide, besides heating
capacity, also excellent cooling capacity.
▪ Efficiency. Under  floor heating has the best performance with
Altherma LT.
▪ Comfort. The combination of the two heat emitter types provides:
▪ The excellent heating comfort of the under floor heating
▪ The excellent cooling comfort of the heat pump convectors
5.2.2
Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example: If the heat  pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Under floor heating or radiators – Thermostatic
valves
If you are heating up rooms with under floor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface or an
external room thermostat), while the other rooms are controlled by
so-called thermostatic valves, which open or close depending on the
room temperature.
Setup
A
Main leaving water temperature zone
EPGA11~16DAV3 + EABH/X16DA6V+9W
Value
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
A
B
C
T
a
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10