Vertical Vent Termination
The Jøtul GF 200 DV IPI can be vertically vented through
a ceiling or to a roof termination with the following
guidelines:
Vertically terminated vent runs require 4/6 vent pipe.
Use Vertical Vent Adaptor Kit 157674. See figs. 13 and 14.
Remove the Burner Skirt Cover Plate and install the Air
Deflector plate to the underside of the Burner Skirt as
shown in fig. 12.
The termination should fall within the shaded areas of
the grids depicted in the Vent Matrix, fig. 9, page 9.
Total run must not exceed 20 ft. (6.09 m).
Vent Terminus Clearance: In no case shall any
discharge opening on the cap be less than 18 in.
(457 mm) horizontally from the roof surface. See fig. 15.
Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or
promote draft reversal. Increasing the height of the
vent may alleviate these conditions.
Use Wall Straps to support an offset pipe run at
intervals of three feet to avoid excessive stress on the
offsets.
Elbows: Four 45°, or two 90° elbows may be used.
Do not include the 45° elbow attached to the stove.
Whenever possible use 45° elbows instead of 90°
elbows as they are less restrictive to exhaust gas and
intake air flow.
A firestop is required at every floor. The floor opening
should be framed to 10" X 10" inside dimension.
Any venting that is exposed in living space above the
first floor must be enclosed. Always maintain the
required 1" clearance from all sides of the vertical vent
system. Insulation in attic space must be retained by
an insulation barrier.
Figure 13. Remove rear shroud to access the Adaptor Collar.
Figure 14. Remove the 5/8 Adaptor Collar components and
replace with the 4/6 collar parts.
Horizontal Overhang
18”.
min.
Termination
Cap
18” min.
Figure 15.
Vertical vent termination height above roof.
139587_05 GF 200 DV IPI October 2015
Use magnetic
retrieval tool to keep
screws for reuse.
18”.
min.
Lowest Discharge
Opening
11