Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the Liebert NX from excessive moisture (see 6.2 - UPS Environmental).
NOTE
If the battery cabinet must remain disconnected from power for more than six (6) months, the
battery must be recharged before use. To charge the batteries, the battery cabinet must be
connected to the Liebert NX UPS and the UPS must be connected to utility power and started
up because the charger operates only while the Liebert NX UPS is operating
NOTE
When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the
UPS—dictates the designed maximum ambient operating temperature.
2.3

Preliminary Checks

2.3.1

Identification

The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.
2.4

UPS Location

2.4.1

Positioning the UPS

Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
2.4.2

Environmental Considerations

Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions
stipulated in 6.2 - UPS Environmental, paying particular attention to the ambient temperature
and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating
temperature within the range of 74-80°F, (23-27°C).
The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit
and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or
cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit
must be a minimum of 8 in. (203mm).
See Table 7 for details on heat dissipation.