10.2

Mimic Display Indicators

The Mimic display on the front panel consists of six indicators arranged in a single-line diagram
depicting the various paths of UPS power, as shown in Figure 54.

Figure 54 Mimic display indicators location

Bypass indicator
Inverter indicator
Rectifier indicator
Battery indicator
Status indicator
The current operational status of the Liebert NX is indicated by the color of the indicators—green,
amber or red—and whether they are ON (solid), flashing or OFF. Table 27 provides a guide to
interpreting the various states of the indicators.
Table 27
Mimic display status indicators
Indicator
(see
Figure 54)
Green
Rectifier
Load on rectifier
Battery powering
Battery
the load
Inverter powering
Inverter
the load normally
Load on Bypass
Bypass
power
Load
UPS output on
No alarms—UPS
Status
working normally
* Battery or battery converter abnormal events include these event messages (see Appendix A): No Battery, Battery Replaced, Battery
Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
®
Liebert
NX
Load indicator
LED1
LED4
LED2
LED5
LED3
Buzzer
STATUS
Flashing Green / Amber
Flashing Green: Utility normal,
but rectifier not operating
Flashing Green: Battery pre-
warning (low battery)
Flashing Green: Inverter on
standby
Amber: UPS has a general
alarm
Operator Control and Display Panel
Liebert NX
2007-01-06
09:20:37
80kV A-3X 3
S ingle
Norm al
Main
Bypass
Output
L 2-N/ L3
L 3-N/ L1
L1-N/L 2
L-N current (A)
71. 4
70.8
71.3
Frequency (HZ)
59. 9
59.9
59.9
L-L voltage (V )
480
480
480
0.99
P owerFactor
0. 99
0. 99
Input disconnect closed
01-06 09:15
Output disconnect closed
01-06 09:15
Bypass abnorm al
01-06 09 :15
?
F1
F2
F3
F4
HELP
Red
Rectifier fault
Battery or battery
converter abnormal*
Inverter fault
Bypass out of
normal range
UPS output
overloaded
UPS has a serious
alarm
81
EPO
INVER TER OFF
FAULT C LEAR
SILENC E ON/ OFF
INVER TER ON
Off
Rectifier is normal, but utility is
abnormal
Battery and converter are
normal, and battery is not
discharging
Inverter normal, but off
Bypass Normal
UPS no output power