IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Electromagnetic Compatibility This manual contains important instructions that should be closely followed during installation of This equipment complies with this Extended Battery Cabinet. requirements of the EMC directive 89/336/EEC, This product is designed for commercial/industrial the published technical standards and Class A use only.
GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage Standby No telecommunication connection...
GENERAL DESCRIPTION System Description Features: The Extended Battery Cabinet is a modular • Up to four Extended Battery Cabinets can be cabinet intended for use with the Nfinity™ modular used with a single Nfinity UPS UPS system. The cabinet will hold a maximum of •...
(kg) in (mm) mishandling or damage. If any damage is noted, call your local Liebert representative and/or notify 52" x 20" x 28" your carrier. (427) (1320 x 508 x 711) Environment Check to make sure that your Extended Battery...
UNLOADING Unloading the Extended Battery Cabinet CAUTION This battery cabinet is heavy (see weight on previous page). At least two people should be present to unload it from the pallet. 1. Once the Extended Battery Cabinet is near the desired operating location, remove the card- board cover.
Optional Stationary Mounting 5. Once the Extended Battery Cabinet is in the desired location, adjust the leveling feet to For greater stability, use a higher-grade bolt. Refer secure its position. to the dimensions below when drilling holes for stationary mounting. 4.75”...
INSTALLATION Grounding DC Power The Extended Battery Cabinet must be installed DC connection with the UPS unit must be via the with a dedicated grounding electrode conductor factory-supplied battery cables, or if longer (GEC) to the site grounding system in accordance connection cable is required, via the optional with national and local wiring codes and regulations Extended Battery Cable kits.
Configuration Setting Scroll down to Intellislot Battery Ca.; select it by pressing For the UPS system to be aware of the presence Change Settings of the Extended Battery Cabinet(s), the system configured with necessary Input Voltage information. To enter the information, follow the Frequency Sync Range Frequency Slew Rate steps below:...
4. Dispose of the removed module in an environmentally responsible way that complies with local codes and regulations or return the module to Liebert for proper disposal. NOTE Battery modules may contain shipping WARNING screws. These screws may be removed and discarded.
Replacing Modules 1. Lift the module to the appropriate bay, resting the end of the module on the bay shelf. Use caution not to rest the module on the lower bezel cover. 2. Push the module into bay. Once it is half way in, slide the module sideways toward the center of the unit.
BATTERY RUN TIMES Internal and Extended Battery Cabinets (minutes) Quantity of Quantity of Battery Modules Extended Battery Cabinets Load VA Load Watts 20,000 14,000 19,500 13,650 19,000 13,300 18,500 12,950 18,000 12,600 17,500 12,250 17,000 11,900 16,500 11,550 16,000 11,200 15,500 10,850 15,000...
Page 18