Table 42 Cable Size Tightening Torque At Liebert Nx 100Kva Ups Terminals; Table 43 Cable Size Tightening Torque At Liebert Nx 120Kva Ups Terminals; Table 44 Cable Size Tightening Torque At Liebert Nx 160Kva Ups Terminals; Table 45 Cable Size Tightening Torque At Liebert Nx 200Kva Ups Terminals - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Table 42
Cable size tightening torque at Liebert NX 100kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 43
Cable size tightening torque at Liebert NX 120kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 44
Cable size tightening torque at Liebert NX 160kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 45
Cable size tightening torque at Liebert NX 200kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 46
Cable size tightening torque at Liebert NX 480V Battery Cabinet DC input bus terminals
Cabinet
Rating
(Copper Wire Only)
225A
350A
600A
All control wiring and power wiring must be 600V rated wire.
®
Liebert
NX
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
4/0
4/0
2/0
2/0
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
250
250
4/0
4/0
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
2-3/0
2-3/0
2-3/0
2-3/0
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
2-4/0
2-4/0
2-4/0
2-4/0
Cable Size
Torque to Tighten
Terminal Bus and Lug Body
4/0AWG
400kcmil
2-350kcmil
Torque to Tighten
10 N-m
10 N-m
10 N-m
10 N-m
Torque to Tighten
10 N-m
10 N-m
10 N-m
10 N-m
Torque to Tighten
26 N-m
26 N-m
26 N-m
26 N-m
Torque to Tighten
26 N-m
26 N-m
26 N-m
26 N-m
15 N-m
15 N-m
26 N-m