Figure 43 Outline Drawing, Liebert Nx 480V 49" Parallel Cabinet - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Figure 43 Outline drawing, Liebert NX 480V 49" parallel cabinet

1240
(48.8)
Top
NOTE:
1. All dimensions are in millimeters (in).
2. Eight-inch minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable access plates. Remove access plate punch to
suit conduit size and replace.
5. Color - black.
6. Unit bottom is structurally adequate for forklift handling.
7. M10 threaded mounting holes used for seismic anchoring or floor stand.
NOTE: If floor stand is used, the weight of the unit must be supported under all casters.
8. Each mounting location is supported by two 10 ga. (.135") galvanized steel. The threaded insert is
approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded
into unit.
9. Side panels must be removed from adjacent units that are bolted together.
10. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tighten leveler against
the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
®
Liebert
NX
965
(38)
Right Side
69
Installation Drawings
2000
(78.7)
Front