12.0 O
PTIONS
Several items of optional equipment are available for connection to the Liebert NX UPS.
12.1
Communication and Other User Terminals
The UPS can be integrated into advanced networking environments via UPS monitoring software
such as Microsoft UPS Monitor
Jbus, Liebert SiteScan
automatic and safe shutdown of the server and PCs.
Figure 68 Monitoring board (U2) auxiliary terminal block detail
J8
LCD
J2
J13 J21 J25
BFP INV ACF
X1
12.1.1 Analog Input Interface
At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is
2 percent. "ENV-T" is used for environment temperature detecting.
• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND
12.1.2 Power Output
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to
12V. The maximum current is 500mA.
12.1.3 Liebert IntelliSlot Communication
The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional
communication cards. Liebert IntelliSlot cards communicate via Liebert's proprietary ESP2 protocol
to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other
cards provide dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is
operating.
™
, Liebert MultiLink
™
, Liebert SiteScan 2
J28
J4
J26 J30 J10
EPO
Dry in
MBC
X2
X3
™
, Liebert Nform
™
, SNMP, etc. They allow UPS status monitoring and
J3
J1
Liebert IntelliSlot 2
Liebert IntelliSlot 1
Liebert IntelliSlot 3
BCB
106
™
, Liebert SiteNet
J22
X7
J23
X6
J12
J9
PWR
MODEM
J15
X5
SNMP CARD
J16
J17
X4
X4
J24
NOTE: The black square ()
on each slot indicates Pin 1.
Options
™
, Modbus /
®
™
Liebert
NX