Figure 28 Liebert Nx 160-200Kva Dimensions-Front And Left Side - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Figure 28 Liebert NX 160-200kVA dimensions—front and left side
48.9 (1242)
FRONT
38.9 (987)
To Centers of Caster Brkt. Typ
1.9 (49)
Front
Front Frame
32.3 x 6.4 (820x163)
Cable Entry Panel
BOTTOM
(Looking Top Down)
NOTES:
1. All dimensions are in inches [mm]. Weight est. 2201 lb. (1000kg).
2. 24" [610] minimum clearance above unit required for air exhaust, and 36" [914] minimum service clearance at front of unit.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring is to be in accordance with national and local electrical codes.
8. Depth dimensions include front door and rear panel.
9. Width dimension includes side panels. Subtract 2.2" (56mm) when removing both side panels.
Table 26
Electrical specifications, Liebert NX 160-200kVA
Rating, kVA
160
200
Source: U3819621, Rev. 1
39.0 (990) to Display
38.5 (978)
RIGHT SIDE
5.0 (127) Typ
5.7 (146) Typ
27.1 (688)
To Centers
of Caster
Brkt. Typ
7.3 (186)
Outside Frame
Voltage
Input
Output
480
480
480
480
61.9
(1573)
Low Voltage
Entry
5.1 x 3.9
(130x100)
2.7 (68)
Front
78.7
Frame
(2000)
See Detail A
REAR
43.7 (1111) Typ.
LEVELER SPACING
Looking Top Down
Heat
Rejection
BTU/hr
35,900
47,000
54
Installation Drawings
.9 (23)
.4 (10)
Outside
Outside
Frame
Frame
TOP VIEW (Door Open)
DETAIL A
1.6 (41) Outside
Frame Typ
1.6 (41) Outside
Frame Typ
3
(76)
4.1 (104)
33.1
(842)
Typ
U3819621
Rev. 1
Cooling Air
CFM
1590
1590
Power Cable
Entry
14 x 13 (355x330)
.8 (19)
Front
Frame
®
Liebert
NX