12.1.4 Communication And Monitoring; 12.1.5 Configuring Baud Rates - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

12.1.4 Communication and Monitoring

Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for
connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status
information and all measured parameters for display through a Web browser.
Table 33
Liebert NX communication options
Physical
description
of port
Top
Liebert
IntelliSlot
Middle
Liebert
IntelliSlot
Bottom
Liebert
IntelliSlot
Top
DB9 port
Bottom
DB9 port

12.1.5 Configuring Baud Rates

The default baud rate for Liebert IntelliSlot cards is 9600. To communicate with the
Liebert OCWEB-LB, Modbus/Jbus or the adapters to permit using Liebert MultiLink, the baud rate
must be set to 2400.
To change the baud rate (refer to Table 33):
1. Use the Navigation keys directly below the LCD to highlight the Settings Screen.
2. Press F1 to move the highlight into the Data & Settings area of the LCD.
3. Use the Navigation keys to scroll down to highlight the current baud rate across from the
appropriate Comm Channel.
NOTE
The Comm Channel settings are not immediately visible because of window-size constraints.
Scroll down to view them on the screen.
4. Press the Enter (F4) key to select the Comm Channel to change.
5. Navigate to underline the desired baud rate (2400).
6. Press the Enter (F4) key to lock in the new baud rate.
®
Liebert
NX
On the UPS
Labeled
LCD screen,
ID Name
under Settings,
of Port
controlled by:
Intellislot 2
(On Monitor
Comm 1
Board)
Intellislot 1
(On Monitor
Comm 2
Board)
Intellislot 3
(On Monitor
Comm 3
Board)
RS232-1
Comm 1
RS232-2
Comm 2
Monitoring
Devices
supported
Multiport 4
Relaycard-int
Liebert IntelliSlot
WEB-LB
Modbus/Jbus
Multiport 4
Relaycard-int
Liebert IntelliSlot
WEB-LB
Modbus/Jbus
Multiport 4
Relaycard-int
Liebert IntelliSlot
WEB-LB
Modbus/Jbus
MultiLink Serial
Service Software
(Reserved)
107
Baud
rate
Comments
any
any
Not simultaneous with
Multilink in RS232-1;
2400
See 12.1.5 - Configuring
Baud Rates
See 12.1.5 - Configuring
2400
Baud Rates
any
any
See 12.1.5 - Configuring
Baud Rates
2400
Not simultaneous with
Multilink in RS232-2
See 12.1.5 - Configuring
2400
Baud Rates
any
any
See 12.1.5 - Configuring
2400
Baud Rates
See 12.1.5 - Configuring
2400
Baud Rates
Not simultaneous with Web
9600
card in top Liebert
IntelliSlot.
Not simultaneous with Web
9600
card in middle Liebert
IntelliSlot.
Options

Advertisement

Table of Contents
loading