Figure 29 Liebert Nx 160-200Kva Dimensions-Front And Left Side - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Figure 29 Liebert NX 160-200kVA dimensions—front and left side
DC
Bus
20.3
(516)
10.6
(268)
FRONT
1.6
(40)
Main Input Bus
See Detail A
BOTTOM VIEW
1. All dimensions are in inches [mm].
2. 24" [610] minimum clearance above unit required
for air exhaust and 36" [914] minimum service clearance at front of unit.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access
plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring is to be in accordance with national and local electrical codes.
8. Terminal connecting hardware included.
®
Liebert
NX
5.9
(150)
10.1
(258)
LOWER
Output
Bypass Input Bus
Bus
(Dual Input)
See Detail A
See Detail A
Rear
Ground
Bus
8
(203)
Typ
RIGHT SIDE FRONT
Right Front Corner
Post Not Shown
BOTTOM CABLE ENTRY
3.9 (100)
Access Plate Height
U389641
Rev. 0
55
Installation Drawings
Ø .39
(10) Typ
1
(25)
Typ
DETAIL A
Input/Output/Bypass
Ø .39
(10) Typ
1
(25)
Typ
GROUND BUS
1
(25)
Ø .39
Typ
(10) Typ
DC BUS