Table 38
External cabinet dimensions, including side panels
Wide Parallel Cabinet
Unit
mm (inch)
1240 (48.8)
Narrow Parallel Cabinet
Unit
mm (inch)
845 (33.2)
33 in. Battery Cabinet
Unit
mm (inch)
845 (33.2)
13.3
Cable size and tightening torques
Table 39
Cable size tightening torque at Liebert NX 40kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 40
Cable size tightening torque at Liebert NX 60kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Table 41
Cable size tightening torque at Liebert NX 80kVA UPS terminals
Bus Type
Main Input
(Single Input)
Main Input
(Dual Input)
Bypass Input
(Dual Input)
Output
Width
Depth
965 (38)
2000 (78.7)
Width
Depth
965 (38)
2000 (78.7)
Width
Depth
965 (38)
2000 (78.7)
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
4
4
4
3
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
1
1
2
2
Cable Size
(Copper Wire Only)
Terminal Bus & Lug Body
2/0
2/0
1/0
1/0
Height
Height
Height
Torque to Tighten
10 N-m
10 N-m
10 N-m
10 N-m
Torque to Tighten
10 N-m
10 N-m
10 N-m
10 N-m
Torque to Tighten
10 N-m
10 N-m
10 N-m
10 N-m
112
Specifications and Technical Data
Liebert
®
™
NX