Clearances; Raised Floor Installation; Cable Entry; Ups Mechanical Characteristics - Liebert Hinet 10kVA User Manual

Hinet ups system 10-30 kva 3x1
Table of Contents

Advertisement

- enough space to easily work on UPS;
- exchange of air sufficient enough to dispel heat produced by UPS;
- protection against atmospheric agents;
- protection against excessive humidity and very high heat sources;
- protection against dust;
- compliance with the current fire prevention norms.
- operative environment temperature within +20° C and +25° C. The batteries are at maximum efficiency in this
temperature range.
2.1.6

Clearances

Cooling air enters the module through ventilation grills located at the bottom of the cabinet and is exhausted through the
fan grills located on the front panel; you must therefore allow for a minimum gap of 170 mm behind the unit to allow
adequate air flow. Clearance around the front of the equipment should be sufficient to enable free passage of personnel
with the door fully opened.
2.1.7

Raised floor installation

If the equipment is to be located on a raised floor it must be mounted on a pedestal suitably designed to accept the
equipment point loading. Refer to the base view to design this pedestal.
2.1.8

Cable entry

Cables can enter for 'Hinet' UPS cabinet from rear side.
2.1.9

UPS Mechanical Characteristics

MECHANICAL
CHARACTERISTICS
Rated power
Height
Width
Depth
Weight:
Hinet cabinet
with 1 battery strings
with 2 battery strings
with 3 battery strings
with 4 battery strings
Unit Shipping Weight
With Standard Battery
Colour
Ventilation
Air flow full speed
Air flow half speed
Protection grade
Cable entry
Page 6
UNITS
kVA
10
mm
mm
mm
275
Kg
320
-
3
m
/h
-
-
15
1220
530
950
185
365
410
RAL 7035 Metal Covers
RAL 7042 Plastic Door
forced
600
300
IP 20
Bottom
(12/01)
Hinet UPS User Manual
20
30
455
545
410
500