fuel loading door. Open the door and measure 8 inches
(203mm) from the side edge of the opening in the face of the
appliance. *See exception.
In Canada, it is necessary to install a fl oor protector of a
minimum of 1 inch (k=0.49, R value= 2.04) of non-combus-
tible material a minimum of 18 inches (457 mm) in front and
8 inches (203 mm) from the sides and rear of the appliance.
*See exception.
*EXCEPTION: Non-combustible floor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
Figure 21.4.
Fuel loading door
8 in.
16 in. from glass
33-5/8 in.
minimum
Figure 21.1
203mm (8 in.)
203mm
(8 in.)
457mm (18 in.)
1092mm (43 in.)
minimum
Figure 21.2
August 3, 2015
44-7/8 in.
minimum
8 in.
USA
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
203m m
(8 in.)
1429mm
(56-1/4 in.)
minimum
CANADA
Fire Risk.
Hearth pads must be installed exactly as specifi ed.
High temperatures or hot embers may ignite
concealed combustibles.
NOTE:
• Illustrations and photos refl ect typical installations and are
FOR DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
• Actual installation may vary due to individual design
preference
• Hearth & Home Technologies reserves the right to alter its
products.
Corner hearth pad dimensions with single
and double wall pipe
53 - 7/8 in.
(1368mm)
Figure 21.3
Figure 21.4
7038-206E
5700 STEP TOP
WARNING
59 - 1/2 in.
(1511mm)
33-5/8 in.
(854mm)
30-1/8 in.
(765mm)
USA
21