Masonry Chimney - Quadra-Fire 57ST-ACC Installation Manual

5700 step top wood stove series
Hide thumbs Also See for 57ST-ACC:
Table of Contents

Advertisement

5700 STEP TOP
F. Masonry Chimney
1 in. (25mm) Clearance
With Firestop
Ceiling Joist
Thimble,
12 in. (305mm)
Of Brick
Floor
Protector
Figure 14.1
WARNING
Fire Risk.
Follow Chimney Connector Manufacturer's
Instructions for Proper Installation.
ONLY use connector:
Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
Attic or roof space
Closet or similar concealed space
Floor or ceiling
Maintain minimum clearances to combustibles
14
Spark Arrestor Cap
Concrete Cap
Rafter
Combustible Wall
Sheathing
Outside Air Rear Vent
Fire Risk.
When lining air-cooled factory-built chimneys:.
Run chimney liner approved to UL 1777 Type HT
requirements (2100 degrees F)
Re-install original factory built chimney cap ONLY
DO NOT block cooling air openings in chimney
Blocking cooling air will overheat the chimney
7038-206E
Fireclay Flue Liner
With Air Space
Flashing
Eave
Outside Air
Termination Cap
Airtight
Cleanout Door
WARNING
August 3, 2015