Cleaning the Combustion Box
Slide baffle forward (30, 40 and 50 models only).
Side insulation panels and rear insulation panel
should be removed to avoid brush damage.
To remove side panel, remove one
screw per panel.
Slide panel down and
away from location.
Rear insulation panel can now be removed.
The heat exchanger can now be easily cleaned
thoroughly. Remove any obstructions from flue outlet
and air inlet. Remove dirt and debris from bottom of
combustion box.
Reassemble all components in reverse order. Check
burner setting pressure and gas rate.
Recommission the boiler before use, checking for gas
soundness and ensuring all controls are working
correctly.
Complete the relevant section of the "Benchmark"
Installation, Commissioning and Service Record Log
Book and hand it back to the user.