Overheat Thermostat - Baxi Solo 2 60 RS Installation And Servicing Instructions

Wall mounted room sealed gas fired central heating boilers
Table of Contents

Advertisement

36

Overheat Thermostat

NOTE: On boilers converted for use with gravity
D.H.W., the overheat thermostat will have been
rendered inoperable and will never need changing.
Loosen the screw on the capillary retaining washer,
allowing the washer to move freely. Free the
capillaries from the clips on the left hand side of the
combustion box. Withdraw the two thermostat phials
from the thermostat pocket.
Remove the locknut and withdraw the
overheat thermostat from the
bracket.
Disconnect the two wires
Reassemble in reverse order. Care must be taken to
align the overheat thermostat capillary with the groove
in the main thermostat phial.
NOTE: The overheat thermostat capillary may be
somewhat longer than necessary. Excess length
should be tidied up by making a neat coil. Contact
with the side of the combustion box should be
avoided.
Reassemble all components in the reverse order to
dismantling.
from the overheat
thermostat and refit them to
the new component.