Site Requirement - Baxi Solo 2 60 RS Installation And Servicing Instructions

Wall mounted room sealed gas fired central heating boilers
Table of Contents

Advertisement

420
5
50
600
50
Aluminium
Shield
12
SITE REQUIREMENTS
The appliance may be fitted to any suitable wall with
the flue passing through an outside wall and
discharging to atmosphere in a position permitting
satisfactory removal of combustion products and
providing an adequate air supply. The appliance should
be fitted within the building unless other-wise protected
by a suitable enclosure ie. garage or outhouse. The
appliance may be fitted inside a cupboard provided that
ventilation requirements and combustible material
standards are adhered to.
If the appliance is fitted in a room containing a bath or
shower reference must be made to the Current I.E.E.
Wiring Regulations and Building Regulations.
If the appliance is to be fitted into a building of timber
frame construction then reference must be made to the
current edition of Institute of British Gas Engineers
Publication IGE/UP/7 (Gas Installations in Timber
Framed Housing).
5
Recommendations for flues are given in BS 5440 Pt1.
A flat vertical area is required for the installation of the
300
If fitted inside a cupboard the clearance of 300mm
shown is only necessary when the cupboard door is
open. A clearance of 5mm (
front of the casing when the door is closed.
NOTE: On gravity applications a clearance of 80mm
(3
1
/
in) is required from the top panel.
8
The following guide lines indicate the general
requirements for siting balanced flue terminals.
If the terminal is fitted within 1 metre (39in) of a plastic
gutter, within 500mm (19
painted gutter, an aluminium shield of at least 1 metre
(39in) long should be fitted to the underside of the
gutter or painted surface. An air space of 5mm (
should be left between shield and gutter.
If the terminal discharges onto a pathway or
passageway, check that combustion products will not
cause a nuisance and that the terminal will not obstruct
the passageway.
If the outer surface of an outside wall is of combustible
material, it should be protected by fitting a non-
combustible plate so that it extends not less than 50mm
(2in) around the terminal.
Location
Clearances
boiler measuring as shown. A space above
the boiler should also be left clear as
indicated by the dotted lines.
These dimensions include the necessary
clearances around the appliance for
case removal, spanner access and air
movement. Additional clearances may
be required for the passage of pipes
around local obstructions such as joists
running parallel to the front face of the
appliance.
3
/
in) is required from the
16
Flue Position
1
/
in) of a painted eave or a
2
3
/
in)
16