Application; Ex Marking; Safety Notes - JUMO ATH-EXx Operating Instructions Manual

Explosion-protected surface-mounted thermostat
Table of Contents

Advertisement

1 Introduction
1.2

Application

1.3

Ex marking

1.4

Safety notes

End of scale
Danger-
°C
reaction
< +200°C
 +200°C
 +350°C
> 350°C
 +500°C
6
Depending on the version, the explosion-protected surface-mounting
thermostat type ATH-EXx can be used as a
TW
temperature monitor
TB
temperature limiter
STW fail-safe temperature monitor
STB break-proof protection temperature limiter
in areas with an explosion hazard caused by gases, vapors or mists, Zone 1 or
in areas with combustible dust or dust/air mixtures, Zone 21.
If this surface-mounting thermostat is used inside the hazardous area, the
relevant regulations for mounting and operating equipment in such an area
must be observed.
Cutting through or kinking the capillary of the surface-mounting thermostat,
type ATH-EXx, will result in permanent failure of the instrument!
Only use the ATH-EXx with TZ 679 in areas that are classified as areas with
low mechanical risk.
II 2G Ex ed IIC T5 bzw. T6
II 2D Ex tD A21 IP65 T95°C bzw.T80°C
Test certificate:
Filling liquid may escape in the event of a measuring system fracture. At present there is
no restrictive statement from the health authorities concerning any danger to health over
short periods and at low concentration, e.g. after a fracture of the measuring system.
Physical and toxicological properties of the substances that may escape in the
event of a system fracture.
Fire and
ous
explosion hazard
Ignition
temp.
°C
+355°C
+490°C
for potentially explosive gas atmospheres
for potentially explosive dust atmospheres
PTB 03 ATEX 1187
CE marking and No. of notified body: CE 0044.
Water
conta-
Explosion
mination
limit
% v/v
0,6 - 8 V
X
- -
X
Toxicological data
irritant
danger to
health
X
X
X
X
– = no; X = yes
toxic