Superior DRL6542TEN Installation And Operation Instructions Manual page 27

Drl 6000 series direct-vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
Superior
DRL6000 Series Direct-Vent Gas Fireplaces
TM
Vertical Vent Figures/Tables
NOTE: If the parameters of your vent run fall outside the parameters described herein, consider installing the Power Vent Kit.
NOTE: Rise per foot run ratios are acceptable all the way to level. For best results, maintain the horizontal/inclined
run in a straight (no dips), slightly elevated plane of approximately 1/4" per 1 ft (20 mm per 1 m).
NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes
through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)firestop/spacer must be used
anytime vent pipe passes through a combustible wall.
NOTE: Two (2) 45° elbows may be used in place of one (1) 90° elbow. The same rise to run ratios, as shown in the
venting figures for 90° elbows, must be followed if 45° elbows are used.
NOTE: An elbow is acceptable as 1 ft of vertical rise, except where an elbow is the only vertical component in
the system.
Do NOT join separate sections of concentric flexible vent pipe.
Figure 26: Top Vent—Straight
Total H = Max. 20 ft (6.096 m)
Total H + Total V = Max. 60 ft (18.3 m)
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 20 for more information.
A 20-ft total Horizontal vent run requires min. 13.5 ft total vertical venting.
Vertical firestop/spacer must be used anywhere vent pipe passes through a combustible floor or ceiling.
u
Horizontal firestop/spacer must be used anywhere vent pipe passes through a combustible wall.
Install the provided vent restrictor, if required.
A 90° elbow may NOT be attached directly to the appliance collar. A minimum of 6" pipe (54" models) or 12"
(42" models) must be used between the fireplace collar and a 90° elbow.
Vertical
Termination
Max. 60 ft
(18 m)
Min. 6 ft
(1.8 m)
Maximum total H
feet
meters
5
1.524
10
3.1
15
4.65
20
6.096
WARNING
Flashing and
Storm Collar
See Clearance to
combustibles on
Page 24
Vertical Firestop/
Spacer
u
Secure Vent
Vent Sections
Minimum total V
feet
meters
3.3
1.006
6.5
1.981
10
3.048
13.5
4.115
Installation
900077-00, 03/2014
27