No. Part name
∗ Attachment
14
TE sensor
(Outdoor
Mount TE sensor on the straight part of the condenser
heat
discharge port pipe so that the lead wire directs upward and
exchange
the sensor directs the liquid store tank.
temperature)
Detail C
∗ Attachment
15
TS sensor
(Suction
Insert TS sensor into the sensor holder welded to the
temperature)
suction pipe and then mount it.
Detail D
∗ Attachment
16
TD sensor
(Discharge
Mount TD sensor on the straight part of the discharge pipe
temperature)
so that the lead wire directs upward and the sensor directs
upward of the cabinet.
Detail E
∗ Attachment
17
TO sensor
(Outside
Insert TO sensor holder claw into the heat exchange
temperature)
terminal block hole and then mount it.
Detail F
Procedure
Heat exchange
TO sensor
terminal block hole
holder
– 144 –
Remarks
Detail F
Detail E
NOTE
NOTE
At working time (finish time), be sure not to
damage the cover of the sensor lead wire with
edge of sheet metal, etc.
If the cover of the sensor lead wire is
damaged, it is dangerous because an electric
shock or fire may be caused.
NOTE
NOTE
After replacing of parts, check the sensors are
mounted at the specified positions.
If there are incorrect mounted positions,
control of the product does not operate
correctly and a trouble may be caused.
Detail C
Detail D