2.3.2 Controls of the Heating Temperature

2.3.2.1 When the heating water temperature is selected
- Setting Temperature: 40 ~ 80
- To stop the run, turns the "HEATING WATER
TEMP." dial to "OFF" position.
2.3.2.2 When the heating is controlled by the room
temperature
- Setting Temperature: 10 ~ 40
- To stop the run, turns the "ROOM TEMP." dial to
"OFF" position.

2.3.2.3 When the heating with the repetition time

(TIMER)
- The timer sets the stop time between 0 to 4-hours.
- Press the "TIMER" button, the boiler runs for 20-
minutes and stops for the time set by the timer.
- The temperature of the heating water is
automatically set at 80
indicator displays the room temperature.
If the range of control has been exceeded due to the change in the set temperature or to abrupt change in
flow, the set temperature will be reached through the proportional control with the delay of 30 3 seconds.
If 83
is exceeded, the delay of 30 3 seconds will not be performed.
Setting Temperature,
"T" set
Over
78
70 ~ 77
60 ~ 69
50 ~ 59
Below
49
and the temperature
ON
63 2.0
"T" set – (14 2.0)
"T" set – (12 2.0)
"T" set – (10 2.0)
"T" set – (10 2.0)
- 8 -
KDB-GOM
Control Range
OFF
83 2.0
"T" set – (6 2.0)
"T" set – (6 2.0)
"T" set – (5 2.0)
"T" set – (5 2.0)
Series