Ignition Failure - Saturn KDB - 161 GOM Manual

Kdb-gom series
Table of Contents

Advertisement

2 - 1
Supply Pressure
Gas Inlet
Measure Hole
Connection
No
Symptoms and Causes
Failure code # 03 indicates ignition failure
of the combustion device
1
In case there is no combustion and failure
code # 03 is displayed
1) Gas supply is not normal.
2) Ignition transformer is not working.
3) Space between electrodes and
discharge.
# 03
Failure
Main Controller
<Fig. 1>
Blue
Ignition
Transformer
<Fig. 2>
Solutions
[Supply pressure standard]
+
50
- LNG : 200
mmH
100
2
- LPG : 280 50 mmH
2
- Check supply pressure and call the gas
company if not normal.
- Check power supply from the controller to the
ignition transformer.
- If there is no power supply, replace the main
controller.
- If there is power supply but the ignition
transformer is not working properly, check for
coil short circuit. If the resistance shows an
infinite level, it is defective and needs to be
replaced.
- The secondary voltage should be 19.5kV and if
it comes out weak, the ignition transformer has
to be replaced.
- Check whether crevice between electrodes is
2~3mm and adjust accordingly.
- Check whether the electrodes are not banded in
a direction.
- 58 -
KDB-GOM

Ignition failure

Electrode Crevice
Electrode
Assembly
O
O
Series
2~3 mm
<Fig. 3>
Reference
<Fig. 1>
<Fig. 2>
<Fig. 2>
<Fig. 3>