Test Operation Function; Forced Maximum / Minimum Combustion Function; Current Proportional Range Compensation - Saturn KDB - 161 GOM Manual

Kdb-gom series
Table of Contents

Advertisement

4.18.2.26 Test Operation Function

- It is priority of the set function of DIP switch.
- Pump operates for 2 hours. In case of open type, operate continuously after auto water filling when low water level is
happens.
- If releases test operation by manipulating DIP switch in standby status after performing test operation and sets again,
initializes test operation function and starts test operation.
- When low water level (pseudo flame) happens in case of closed air type, releasing automatically by the interval of one
minute and progresses continuously.
- When flow switch is ON in case of closed air type, stops pump and checks trouble.
- When DIP switch sets test operation, the power lamp flickers by repetition of ON for 1 second and OFF for 1 second.

4.18.2.27 Forced Maximum / Minimum Combustion Function

- When change-over switch sets to forced Max or forced Min, combusts by the set Max or Min according to the capacity
of the boiler after normal ignition. (PID control doesn't.)
- When DIP switch sets for both forced Max and Min at the same time, combusts by forced Min.
- During combustion of forced Max / Min, operation of stopping time isn't performed.
- If the test operation is ON in status of forced Max/Min operation, the function of forced Max / Min operation isn't work.
4.18.2.28 Fault repair codes(room thermostat, FR-5)
FND No.
01
Overheat
02
Low water level
03
Ignition failure
Flame sensor
04
(Lower gas pressure)
05
Heating sensor wire disconnected
06
Short circuit of heating sensor
07
Hot water sensor wire disconnected
08
Short circuit of hot water sensor
09
Fan R.P.M. failure

4.18.2.29 Current Proportional Range Compensation

- Maximum current change by adjusting variable resistor for maximum current compensation.
- Current compensation range can be variable more than ± 20mA of maximum current.
4.18.4.30 The Others
- Heating flow switch is used to monitor water level of closure type (closed air type).
- Power lamp is always lit in the condition of power ON and flickers by the repetition of ON for 0.5 second and OFF for 0.5
second in the abnormal condition.
4.18.2.31 Secondary Gas Pressure according to Capacity of Boiler (mmAq)
Model
KDB – 161 GOM
KDB – 201 GOM
KDB – 251 GOM
KDB – 301 GOM
Problems
High Load
NG
LP
NG
LP
NG
LP
NG
LP
- 34 -
FND No.
10
Air pressure failure
11
Water level detection failure
12
Flame failure in combustion
13
Heating water switch failure
14
Gas alarm(optional)
15
MICOM failure
16
Mechanical overheat
17
DIP switch setting error
18
104
170
104
150
104
165
106
156
KDB-GOM
Series
Problems
Low Load
20
20
20
30
20
38
20
30