Approved Vent Configurations

Maximum Vent Run and Rise

The fireplace vent must meet the following requirements:
Maximum Horizontal Run = 100' (30 M)*
Maximum Vertical Rise = 140' (42 M)*
Maximum 90˚ Elbows = 4 (note: two 45˚ elbows count as one 90˚ elbow)
Maximum Vertical Drop = 3' (1 M) Below base of fireplace
Minimum Vent Length = 54" (1372mm)
* Those installations with a total vent length over 140' (42 M), contact Travis Industries for further review
and approval.
140 feet (42m)
120 feet (36m)
100 feet (30m)
80 feet (24m)
60 feet (18m)
40 feet (12m)
© Travis Industries
Installation
20 feet (6m)
0 feet
-3 feet (-1m)
(for qualified installers only)
4140717