Set Temperature Correction; Various Setting On Outdoor Unit (Power Save, Cooking-Only, Etc.) - Toshiba RAS-M10PKVP-E Service Manual

Hide thumbs Also See for RAS-M10PKVP-E:
Table of Contents

Advertisement

Item
Operation flow and applicable data, etc.
19. Set temperature
Indoor Control P.C. Board (Factory Default)
correction
20. Various setting
on outdoor unit
(Power save,
Cooling-only,
Power save
etc.)
setup
Cooling-only
setup
Heating-only
setup
Caution:Set the switch before turning on the power supply.
In HEAT Operation
Jumper wire setup
: With Jumper wire
: Cut Jumper wire
The following settings are available by DIP switch setup.
Function
Setting position
Power save function
Select current limit
Cooling only setting
Heating only setting
1. Purpose
When the difference between the set temp. of
the remote controller and the room temp. is
wide due to the installation condition, etc, the
Jumper wire
set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the remote
controller is corrected.
The correct value from –2°C to +4°C is changed
by the jumper wire on P.C. board of the indoor
microcomputer.
HEAT
shift value
← At shipment
Turn the switch to ON, when using the power save function.
SW802
No.1
No.2
Current limit
When using the air conditioner as a cooling-only conditioner,
turn the switch to ON.
(If the heating mode is selected by remote control, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs cooling operation.)
When using the air conditioner as a heating-only conditioner,
turn the switch to ON.
(If the cooling mode is selected by remote control, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs heating operation.)
– 66 –
Description
Control contents
OFF
ON
ON
OFF
ON
ON
OFF
OFF
11A
8.5A
Full
Full (Default)