In Heating Operation - Toshiba RAS-M10PKVP-E Service Manual

Hide thumbs Also See for RAS-M10PKVP-E:
Table of Contents

Advertisement

Item
<In heating operation>
2. Indoor fan
motor control
(This operation controls the fan speed at indoor unit side.)
(Continued)
The indoor fan (cross flow fan) is operated by the phase control
induction motor.
The fan rotates in 5 stages in MANUAL mode, and in 5 stages in
AUTO mode, respectively. (Table 2)
HEAT ON
Fan speed setup
AUTO
TC ≥ 42°C
NO
(Fig. 4)
Basic fan control
TA [°C]
TSC
–0.5
–1.0
–1.5
–2.0
–2.5
–5.0
–5.5
1: Fan speed = (M + -L) × 1/5 + L+
2: Fan speed = (M + -L) × 2/5 + L+
3: Fan speed = (M + -L) × 3/5 + L+
4: Fan speed = (M + -L) × 4/5 + L+
(Calculated with linear approximation from M+ and L+)
5: Fan speed = (H – M) × 1/5 + M
6: Fan speed = (H – M) × 2/5 + M
7: Fan speed = (H – M) × 3/5 + M
8: Fan speed = (H – M) × 4/5 + M
(Calculated with linear approximation from H and M)
Operation flow and applicable data, etc.
MANUAL
Indication
Fan speed
L
L+
(L + M) / 2
M
M+
(M + H) / 2
H
YES
Min air flow rate control
Limited to Min WD tap
Tc
No limit
Fan speed =
(TC – (40 + a)) / 10 × (WD – W8) + W8
a : In up operation 1, in down operation 0
Fan speed
Hi Power
L+ (W9)
M (WB)
M+ (WD)
H (WE)
(Fig. 5)
(Fig. 3)
Hi Power
W8
W9
(L + M) / 2
WB
WD
(M + H) / 2
WE
WF
Tc
No limitation while fan speed MANUAL mode is in
stability.
A: When Tsc
24, A is 24, and when Tsc < 24, A is Tsc
Tsc: Set value
– 52 –
Description
1) When setting the fan speed to L, L+,
M, M+ or H on the remote controller,
the operation is performed with the
constant speed shown in Fig. 3 and
Table 2.
2) When setting the fan speed to AUTO
on the remote controller, revolution of
the fan motor is controlled to the fan
speed level shown in Fig. 5 according
to the set temperature and room
temperature.
3) Min air flow rate is controlled by
temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4.
4) Cold draft prevention, the fan speed
is controlled by temperature of the
indoor heat exchanger (Tc) as shown
in Fig. 6.
Cold draft preventive control
H (WE)
Line-approximate
H and SUL with Tc.
SUL (W2)
Stop
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
(Fig. 6)