Item
2. Indoor fan
motor control
(Continued)
FAN AUTO
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation start
and room temp. is 3°C or lower than set temp.
FAN Manual
• Room temp. < Set temp. –4°C
RAS-M10PKVP-E
Fan speed level
Fan speed
(rpm)
WF
1140
WE
UH
1140
WD
H
1070
WC
M+
980
WB
900
WA
M
850
W9
810
W8
L+
710
W7
L
710
W6
L–
650
W5
UL
650
W4
650
W3
SUL
650
W2
560
W1
420
Operation flow and applicable data, etc.
[In starting and in stability]
In starting
(Table 2) Indoor fan air flow rate (Heating)
RAS-M13PKVP-E
Air flow rate
Fan speed
3
(m
/h)
(rpm)
640
1200
640
1200
590
1100
530
1010
470
930
430
850
400
810
330
710
330
710
290
650
290
650
290
650
290
650
220
560
120
420
• When 12 to 25 minutes passed after operation start and
room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
• Room temp. ≥ Set temp. –3.5°C
RAS-M16PKVP-E
Air flow rate
Fan speed
Air flow rate
3
(m
/h)
(rpm)
690
1280
690
1280
610
1180
550
1090
490
980
430
900
400
880
330
780
330
710
290
700
290
650
290
650
290
650
220
560
120
420
– 53 –
Description
In stability
RAS-M18PKVP-E
Fan speed
Air flow rate
3
(m
/h)
(rpm)
(m
750
1390
805
750
1390
805
670
1290
730
610
1180
655
530
1070
575
470
980
510
450
950
490
380
850
420
330
850
420
320
700
310
290
650
275
290
650
275
290
650
275
220
560
210
120
420
110
3
/h)