Venting Arrangements; Horizontal Termination (Flex) - Regency Fireplace Products Gem54-NG Owners & Installation Manual

Gem54 series gas fireplace
Table of Contents

Advertisement

These venting systems, in combination with the Gem54, have been tested and listed as a direct vent system by AGA. The location of the termination
cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FpI Direct vent (Flex) System Termination kits include all the
parts needed to install the Gem54 using a flexible vent.
FpI kit #
Length contains:
#946-615
4 Feet
1)
(1.2 m)
2)
3)
4)
#946-618
6 Feet
5)
(1.8 m)
6)
7)
#946-616
10 Feet
8)
(3 m )
9)
10) vinyl siding standoff
Regency Gemfire™ Gas Fireplace

vENTING ARRANGEMENTS

HORIZONTAl TERMINATION (FlEX)

Regency
8" (203mm) flexible liner (Kit length)
5"(127mm) flexible liner (Kit length)
spring spacers
thimble
AstroCap termination cap
screws
tube of Mill Pac
plated screws
S.S. screws #8 x 1-1/2" (38mm) drill
point
Wall Thimble
(Mandatory in all
Horizontal Terminations)
5" dia. flue pipe
8" dia.
Flue pipe
Direct vent System
®
Vinyl Siding
Standoff
AstroCap XL
Termination Cap
(Part #946-623/P)
spring spacer
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal vent must be supported every 3 feet (0.9m).
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.