Switching The Status Display On The Bc10 To Show The Boiler Temperature Status; Recording Actual Values - Buderus Logano plus GB312 Installation And Maintenance Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

Gas train boiler size 200 to 280 kW
B Wait until 30 % burner output is achieved.
B Check the CO
content.
2
Insert the test probe through the test port into the core
flow inside the flue.
B At CO
values below 9.0 % or in excess of 9.6 %, set
2
adjusting screw N [3] to 9.3 %.
– Turning clockwise increases the CO
– Turning anti-clockwise reduces the CO
Fig. 39 Correct the CO
2
(boiler size 200 to 280 kW)
1
Apertures for adjusting the gas train
2
Adjusting screw V (sealed)
3
Adjusting screw N (sealed)
4
Gas train
B Recheck the CO
content and enter the value in the
2
commissioning report, Chapter 6.23.
6.15 Switching the status display on the
BC10 to show the boiler
temperature status
B Press
to change to the next status display.
The current operating pressure P1.7 is displayed.
B Press
to change to the next status display.
Operating status 0Y (display code) is shown.
B Press
to change to the next status display.
The boiler temperature is displayed.
6.16 Returning to operating mode from
the flue gas test
B Press
to terminate the flue gas test.
B Return to the operating mode at the RC35
programming unit.
B Close the flap on the RC35 programming unit.
Logano plus GB312 - Subject to technical modifications.
content.
2
content.
2
content under partial load
B If the boiler is intended to be operated with the
Logamatic 4000 control system, remove the RC35
programming unit again. Start the Logamatic 4000
control system.

6.17 Recording actual values

B Carry out the following tests at a test port in the boiler
flue connection and enter the results in the
commissioning report (
– Draught
– Flue gas temperature t
– Air temperature t
L
– Net flue gas temperature t
– Carbon dioxide content (CO
or oxygen content (O
– CO value
Fig. 40 Recording actual values
1
Position of the test port in the flue
6.17.1 Draught
The required draught for the installed flue gas/ventilation
air system must not exceed 100 Pa (1.0 mbar).
DANGER: Risk to life from toxic flue gases
escaping.
B Only operate the boiler with a chimney or
flue system (
6.17.2 CO value
CO values in an air-free state must be below 400 ppm or
0.04 % vol.
Values above 100 ppm indicate an incorrect burner
adjustment, incorrect appliance setup, burner and/or heat
exchanger contamination or burner faults.
B Identify and eliminate the cause.
Commissioning
Chapter 6.23):
A
- t
A
L
)
2
)
2
Tab. 7, page 10).
6
37