Buderus Logano plus GB312 Installation And Maintenance Instructions Manual page 47

Gas condensing boiler
Table of Contents

Advertisement

Fig. 51 Permissible pressure drop per minute during the internal tightness test with prevailing gas supply pressure
x
Test volume in litres
y
Test volume in mbar within one minute
1
Range "Valve tight" = applies to new installations
2
Range "Valve adequately tight" = valve can be used
without restrictions
3
Range "Valve leaks" = valve may not be used
>> check as described in the following
Read-off example: test volume (V
pressure drop 4 mbar/min = range 3 "Valve leaks" = valve
may not be used >> check as described in the following
If you detect a steep pressure drop of
> 10 mbar/minute at a test volume of (V
of < 1, increase the test volume (V
For this, include the pipework to the next
shut-off valve in the tightness test and repeat
the test using the new test volume (V
If the read-off point for test volume (V
drop per minute lies within the range "Valve leaks" (see
read-off example), carry out the test described below.
NOTICE: System damage!
B Never spray or let leak detection agent
drip onto cable entries, plugs or electrical
cables/leads.
B Cover areas at risk before testing for
leaks.
B Check all sealed points in the tested pipework section
using a foaming leak detection agent.
B If required, seal any leaks and repeat the test.
B If no leaks are found, replace gas train.
Completing the leak test
B Remove hose.
B After completing the test, fully tighten the screw inside
the pressure test nipple.
B Check the pressure test nipple for tightness.
Logano plus GB312 - Subject to technical modifications.
) 5 litres and
test
)
test
).
test
).
test
) and pressure
test
Inspection and maintenance
9
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents