Conversion For Boiler Size 160 Kw; Conversion For Boiler Sizes From 200 To; Updating The Type Plate - Buderus Logano plus GB312 Installation And Maintenance Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

6.5.2

Conversion for boiler size 160 kW

The boiler size 160 kW is not equipped with a gas
restrictor. Consequently, the conversion is achieved via
the full load adjusting screw.
Converting from gas type H to gas type L:
B Rotate full load adjusting screw [1] one half turn anti-
clockwise.
Converting from gas type L to gas type H:
B Rotate full load adjusting screw [1] one half turn
clockwise.
Fig. 25 Conversion to a different gas type (boiler size
160 kW)
1
Full load adjusting screw
6.5.3

Conversion for boiler sizes from 200 to

280 kW
Converting from gas type H to gas type L:
B Increase the value of adjusting screw V (
by 0.5, e.g. from setting 1.1 to 1.6.
Converting from gas type L to gas type H:
B Decrease the value of adjusting screw V (
[2]) by 0.5, e.g. from setting 1.6 to 1.1.
Logano plus GB312 - Subject to technical modifications.
Fig. 26 Conversion to a different gas type (boiler size
1
Apertures for adjusting the gas train
2
Adjusting screw V (sealed)
3
Adjusting screw N (sealed)
4
Gas train
6.5.4
B Affix label [2] (supplied with the boiler) in the respective
area over type plate [1] (on the side panel).
Fig. 26, [2])
Fig. 26,
Fig. 27 Updating the type plate
1
Type plate
2
Label (gas values)
Commissioning
200 to 280 kW)

Updating the type plate