Setting The Boiler Water Temperature - Buderus Logano plus GB402 Operating Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

3
Operation
3.2.2

Setting the boiler water temperature

B Select the upper temperature limit for the boiler water
in heating mode with the maximum boiler water
temperature rotary selector [1] according to Tab. 3.
NOTICE: System damage in underfloor
heating systems through overheating the
pipework!
B For underfloor heating systems, never set
the boiler water temperature higher than
40 °C.
To save energy, set the maximum boiler water
temperature low enough that it is still
sufficiently warm inside the building.
The required room temperature cannot be
achieved if this temperature is set too low.
For further details regarding energy saving,
see the programming unit or control unit
operating instructions.
Controller position
0
40
75 – 90
90
Aut
Tab. 3 Settings at the maximum boiler water temperature rotary selector
10
Setting for
Underfloor heating system
Radiators
Convector heaters
Underfloor heating
Radiators
Convector heaters
Fig. 4
Base controller user interface
1
Rotary selector for maximum boiler water temperature
Explanation
Heating operation is switched OFF (poss. only DHW operation).
Required boiler water temperature in °C
The temperature is established automatically with a programming
unit RCxx using the heating curve. If no programming unit is
connected, the maximum boiler water temperature is 90 °C.
Logano plus GB402 - Subject to technical modifications.
1
6 720 617 694-05.1RS